Product Introduction
The ECNITY EC forward curved centrifugal blower offers a high level of intelligent control. Integrated electronic control modules support multiple control modes, including constant airflow, constant pressure, and constant power, allowing precise adaptation to various ventilation requirements. Supported control interfaces include 0–10V / 4–20mA analog signals, PWM control, and RS485 communication. These blowers can integrate with building automation and environmental monitoring systems, enabling remote monitoring, speed regulation, and fault alarms for centralized management.

EC forward curved centrifugal blower technical parameters:
|
Model No. |
Rated |
Operation Voltage |
Frequency |
Rated |
Rated Power |
Rated |
Air Flow |
Air |
Noise |
|
VAC |
VAC |
Hz |
A |
W |
RPM |
m3/h |
Pa |
dBA |
|
|
EN-F120-H062-E115-A01 |
115 |
90~135 |
50/60 |
0.80 |
55 |
2400 |
280 |
400 |
59 |
|
EN-S120-H062-E115-A01 |
|||||||||
|
EN-F120-H062-E230-A01 |
230 |
184~274 |
50/60 |
0.40 |
55 |
2400 |
280 |
400 |
59 |
|
EN-S120-H062-E230-A01 |
Outline Drawing:

Performance Curve

Connection
|
DC Wire |
AC Wire |
||
|
Color |
Function |
Color |
Function |
|
Red |
+10VDC |
Brown |
L |
|
Blue |
GND |
Blue |
N |
|
Yellow |
0~10VDC/PWM |
Green/Yellow |
PE |
|
White |
FG |
||
Case of EC forward curved centrifugal blower: Precision Laboratory Ventilation System
A university materials science laboratory conducting nano-material and polymer research required extremely high airflow precision, stability, and electromagnetic compatibility.
The laboratory installed 12 EC single-inlet centrifugal blowers. Local exhaust ventilation used models with airflow of 500–800 CFM and ±5% control accuracy, operating in constant pressure mode to ensure safe and stable removal of hazardous gases. System-level ventilation used models with electromagnetic shielding to resist external interference while minimizing self-generated emissions. Remote monitoring enabled real-time tracking of speed, temperature, and pressure, with instant alarms in case of anomalies.
After 18 months of continuous operation, the system experienced zero failures, achieving 100% airflow stability compliance and fully meeting laboratory ventilation requirements.

Our factory


















FAQ
1. Are EC centrifugal fans suitable for packaged HVAC units?
EC centrifugal fans are widely used in packaged HVAC units. Integrated electronics simplify system design. Variable speed operation improves efficiency. They support compact and efficient unit construction.
2. Can EC fans be applied in customized ventilation solutions?
EC fans are suitable for customized ventilation solutions. Flexible control and configuration support special requirements. They are commonly used in project-based systems. Early technical coordination improves results.
3. What after-sales support is available for EC centrifugal fans?
After-sales support typically includes technical assistance and documentation support. Customers can receive guidance for installation and operation issues. Support availability depends on supplier policy. Reliable after-sales service helps ensure long-term operation.