Product Introduction
The ECNITY 133mm EC Double inlet centrifugal fan is based on Electronically Commutated (EC) technology, combining the convenience of AC power supply with the high efficiency of DC motor operation. It represents a new generation of ventilation equipment that balances energy efficiency and intelligent control.
Featuring a symmetrical double-inlet design, the inlet area is effectively doubled compared to single-inlet models. This allows air to enter the impeller more evenly, significantly reducing energy losses caused by airflow turbulence while simultaneously lowering vibration and noise. The motor adopts permanent magnet synchronous technology and operates without mechanical carbon brushes, achieving an energy conversion efficiency of over 90% and delivering 30–70% energy savings compared with traditional fans. The blower fully complies with stringent global energy efficiency regulations such as the EU ErP Directive.

133mm EC Double inlet centrifugal fan technical parameters:
|
Model No. |
Rated |
Operation Voltage |
Frequency |
Rated |
Rated Power |
Rated |
Air Flow |
Air |
Noise |
|
VAC |
VAC |
Hz |
A |
W |
RPM |
m3/h |
Pa |
dBA |
|
|
EN-D133-H190-E115-A01 |
115 |
90~135 |
50/60 |
1.80 |
120 |
1400 |
900 |
290 |
67 |
|
EN-D133-H190-E230-A01 |
230 |
184~274 |
50/60 |
0.90 |
120 |
1400 |
900 |
290 |
67 |
Outline Drawing:

Performance Curve

Connection
|
DC Wire |
AC Wire |
||
|
Color |
Function |
Color |
Function |
|
Red |
+10VDC |
Brown |
L |
|
Blue |
GND |
Blue |
N |
|
Yellow |
0~10VDC/PWM |
Green/Yellow |
PE |
|
White |
FG |
||
An integrated intelligent control module supports 0–10 V / PWM analog control as well as MODBUS digital communication, enabling dynamic speed adjustment according to real-time load conditions. This allows precise matching of airflow and static pressure requirements. 133mm EC double inlet centrifugal fan blowers are widely used in central HVAC systems for commercial complexes, industrial workshop ventilation, and other medium- to large-scale applications.
From a fundamental perspective, the key advantage of 133mm EC double inlet centrifugal fan lies in electronic commutation technology, forming an integrated system of "AC input – DC drive – intelligent control." Grid AC power is internally converted to DC, and electronic circuitry precisely controls motor commutation and speed. Stepless speed regulation is achieved without an external frequency inverter, reducing additional energy losses.
DC double inlet centrifugal blowers rely on the electromagnetic induction principle of DC motors. DC current generates a constant magnetic field that drives rotor rotation and impeller motion. Brushed models use mechanical carbon brushes for commutation, while brushless models rely on Hall sensors or sensorless vector control. Their simpler structure and control logic make them suitable for basic ventilation applications with lower speed-control precision requirements.

Our factory


















FAQ
1. Can EC fans be used in residential ventilation systems?
EC fans can be used in residential ventilation systems. Quiet operation and speed control improve comfort. Energy efficiency supports long-term operation. Selection should match system size.
2. Are EC fans suitable for OEM ventilation equipment?
EC fans are widely used in OEM ventilation equipment. Compact design simplifies integration. Integrated control reduces external components. This supports standardized OEM production.
3. Can EC centrifugal fans be used in industrial process cooling?
EC centrifugal fans are suitable for industrial process cooling. They provide reliable airflow under continuous operation. Speed control allows adaptation to process demand. Proper specification ensures stable cooling performance.
4. Are EC fans suitable for laboratory ventilation systems?
EC fans are used in laboratory ventilation systems when properly specified. Stable airflow control supports safety requirements. They can be integrated with monitoring systems. Application conditions must be clearly defined.