After the axial flow fan is installed, before starting it, check the fan's rotational flexibility by manually rotating the blades to ensure there is no jamming or friction. Check for any remaining objects or debris inside the fan and adjacent ductwork.
Check that the dampers in the ductwork are in the open position.
Personnel should stay away from the fan.
Start the fan and check if the direction of rotation of the blades matches the rotation indicator mark. After confirming this, run the fan for 10-30 minutes, then stop it and check for any loose blades or loose bolts connecting the vibration isolator to the base. Only after everything is confirmed to be normal should the fan be officially started and put into operation.