Preparation
Unpack and inspect all components of the fan to ensure they are complete. Check the fan casing for any damage, paying particular attention to the head rectifier for any dents or deformation. Ensure all components are securely connected, the fan blades and motor are undamaged, and the impeller rotates freely. Repair and adjust any problems found. Inspect the fan's mounting base; it must have sufficient strength and rigidity to withstand the fan's operating load. Also, check that the connection dimensions between the base and the fan meet the design requirements.
Installation Instructions
For horizontal floor mounting, fix the vibration isolators to the fan base using connecting bolts. Adjust the horizontal height of each vibration isolator using center height adjustment shims. Secure the fan to the connecting steel plate, which has been welded to the foundation, using fixing bolts. If vibration isolators are not required due to seismic considerations, the bolt holes on the fan base can be directly connected to the pre-embedded bolts in the foundation.
For side wall horizontal mounting, the basic requirements are the same as for horizontal floor mounting, except that the mounting bracket is a slanted arm support type. The bracket must have sufficient strength and rigidity. This installation method is not recommended for fans larger than size 10#.
For suspended mounting, connect the vibration isolators to the fan using bolts. The vibration isolators should be symmetrically installed on both sides of the fan's center of gravity. Lift and insert the fan into the suspended bracket. The height of the suspended bracket is determined by the user based on the actual space requirements. This installation method is generally not used for fans larger than size 16#.
For vertical mounting, the installation method is the same as for horizontal floor mounting, but the requirements for the strength and rigidity of the fan foundation are more stringent.
Flexible connectors must be used to connect the fan to the pipelines at both ends to isolate vibration and protect the fan.