Centrifugal fan commissioning methods

Jan 01, 2026

Leave a message

A centrifugal fan is a complex piece of equipment, mainly composed of an air inlet, damper, impeller, motor, and air outlet. The performance of a centrifugal fan varies under different conditions. Therefore, the performance of the centrifugal fan is affected by the operating conditions of its different parts. Optimizing the performance of a centrifugal fan can be achieved through several approaches.

 

Centrifugal fans allow for full-voltage or reduced-voltage starting, but it should be noted that the current during full-voltage starting is approximately 5-7 times the rated current. The starting torque during reduced-voltage starting is proportional to the square of the voltage. When the power grid capacity is insufficient, reduced-voltage starting should be used.

 

During the commissioning of a centrifugal fan, the product manual should be carefully read, and the wiring method should be checked to ensure it matches the wiring diagram; the operating voltage of the power supply to the fan should be carefully checked to ensure it meets the requirements, that there is no phase loss or phase difference, and that the capacity of the electrical components is sufficient.

 

During commissioning, there should be at least two people: one controlling the power supply and the other observing the fan's operation. Any abnormal phenomena should result in immediate shutdown and inspection; first, check if the rotation direction is correct; after the centrifugal fan starts running, immediately check whether the operating current of each phase is balanced and whether the current exceeds the rated current; if there are any abnormal phenomena, stop the machine and inspect it. After five minutes of operation, stop the machine and check for any abnormal phenomena. Only restart the machine after confirming that there are no abnormalities.

 

When commissioning a dual-speed centrifugal fan, the low speed should be started first to check if the rotation direction is correct; when starting at high speed, the fan must be completely stopped before starting again to prevent reverse rotation at high speed, which could cause the switch to trip and damage the motor.

 

When the centrifugal fan reaches its normal speed, the fan's input current should be measured to ensure it is within the normal range. The operating current of the centrifugal fan should not exceed its rated current. If the operating current exceeds the rated current, the supplied voltage should be checked to ensure it is normal.

 

The required motor power for a centrifugal fan refers to the power required under certain operating conditions, with the air inlet fully open, which requires a larger power. If the fan is operated with the air inlet fully open, there is a risk of motor damage. During fan commissioning, it is best to close the valves on the fan's inlet or outlet pipes. After starting the fan, gradually open the valves until the desired operating conditions are reached, and pay attention to whether the fan's operating current exceeds the rated current.

 

By strictly following the above commissioning method for centrifugal fans, the efficiency of the centrifugal fan can reach over 98%.